Click Here to Return to POWER PLANT INDEX

112 MW GAS TURBINE PACKAGE
For Sale as Turnkey Project 
Call for Price
Two General Electric Company (GEC)  Model EM610B Gas Turbine Generator sets
58.7MW base load, 61.9MW peak load 50Hz 11.8 KV Fuel Diesel #2
Contact Milt Fyre for more details.
Phone: 503-595-5418   
Email: milt@rmaglobal.com

The output will be 112 MW. The transformers are duel wound. One at either 132 KV or 33 KV and the other at 132 KV or 66 kV. The only items not including in the move are the civil work, the transport from the docks to the site, and the erection labor. All erection and commissioning supervision will be included.  the plant is presently dismentled. 

Two operational GEC EM610B 50Hz gas turbine generator sets featured with:

o 13 stage compressor and 2 stage power turbine, single shaft supported by 2 bearings
o 3.3 KV motor starter
o 2-pole, 3 phase 50Hz 11.8 KV 72.5 MVA air cooled generator
o Brushless exciter control system
o 11.8/132 KV 80 MVA OFAF generator transformer with on load tap changer
o 11,800/433 V 250KVA ONAN unit transformer
o 110V AC inverter with battery / charger system
o High scanning speed temperature monitoring system with IBM PC Data acquisition program
o Full package of auxiliaries including a workshop
o With a 2.6 MVA black start diesel generator as option

History of the Units
The two model EM610B open cycle, single shaft, gas turbine sets, manufactured by GEC Gas Turbines Limited (UK) and commissioned in 1981. Originally installed in 1980, and operated until 1991, the gas turbine sets were relocated and re-commissioned in 1992. They were available for service through until 1998 when they became surplus to generation requirements. They are currently dismantled under preservation.

The operating hours/starts for the two units are 598/825 and 910/975 respectively.

Design Data
o Base load 58.7MW and peak load 61.9MW under ambient air conditions of 30oC and 1013 mbar
o Corresponding thermal efficiencies for base load and peak load at 25.4% and 27.0 %
o Normal start/Emergency start to synchronise speed total time required at 6.0 min and 6.0 min
o Normal start/Emergency start to peak load total time required at 15.0 min and 9.0 min

1. Gas Turbine
o Single shaft, 2 bearings supported on rigid steel stools
o 13 compressor stage, 2 power turbine stage
o 10 individual reverse flow combustion chambers
o Designed to run on liquid fuel oil
o Mean gas temperature at first row guide vanes at 900oC base / 950oC peak
o Mean gas temperature at turbine exhaust at 503oC base / 541oC peak

1.1 Fuel Specification
o Industrial diesel oil
    Minimum calorific value at 45579 KJ/kg
    Minimum kinematic viscosity 1.6 Cs
    (THE UNITS ARE CAPABLE OF GAS FIRING WITH MODIFICATIONS.)

1.2 Fuel Oil System
o One fuel oil forwarding skid comprises of 3 AC pumps.
o 2 staged filtration and pumping at gas turbine side.
o Hydraulically control fuel throttle valve before combustion chambers.

1.3 Fuel Throttle Valve Control Oil System

o Fed from main lub oil rail powered by AC motor pump
o Dual circuit with filter and accumulator

1.4 Governor
o Mk 2 unified governor system
o Electronic, Electro-hydraulic and Electromechanical units

1.5 Combustion chamber

o Ten combustion chambers fabricated from nimonic 75 alloy
o Permit quick removal for inspection
o LPG ignition, simplex type burner nozzle
o Individually metered and temperature monitored

1.6 Starting Equipment

o 3.3 KV 746KW 1487rpm induction starter motor
o Starter motor coupled through a torque converter to the gas turbine rotor
o Fottinger principal Voith twin disc torque converter

1.7 Lubrication and Jacking Oil System

o Mineral oil BS489 grade 46 total quantity 200Kg
o Shaft driven positive displacement oil pump via auxiliary gearbox
o 1 AC motor centrifugal oil pump
o 1 DC motor centrifugal oil pump for emergency standby
o 2 AC motor jacking oil pumps
o 1 air oil cooler and 1 duplex strainer

1.8 Barring System
o Hydraulic ratchet powered by jacking oil pump
o Automatic Timer control
o Manual control provided

1.9 Cooling Air and Gland Packing System
o Bled from compressor casing, cooled by air blast cooler
o Cool the turbine discs, diaphragms and stator rings
o Pack the turbine end bearing glands

1.10 Intake system

o Turbine intake filter package in a filter house
    Coalescer safety pad
    Duracel high efficiency filter
    Differential pressure switch
    Inlet silencer
    Stainless steel trash screen before turbine inlet
o Generator filter package in a pair of wing houses
    Dust louvre inertial separator
    Amerkleen pad

1.12 Lagging and Cladding
o Intersperse acoustic covers
o Centre, intermediate and turbine casing cladding
o Easy to remove for turbine inspection and maintenance

1.14 Compressed air system
o 1 AC motor driven, air cool, 2 cylinder air compressor
o 1 air receiver

2. Generator
o 2-pole, 3 phase 50Hz 11.8 KV 72.5 MVA air cooled generator
o Class F insulation, delta connection
o Temperature sensors at stator core, windings and air circuit for monitoring
o Full scheme of electrical protection

2.1 Exciter
o Revolving armature Brushless exciter with silicon diodes
o Directly coupled to the generator rotor
o Static circuit AVR
o Manual control channel
o Manual follow-up circuit
o Full automatic protective devices

2.2 SSS ( synochro-self-shifting) Clutch
o Installed between the gas turbine and the generator
o Fully automatic, 'freewheel' device transmits power through gear-tooth element
o Permits the generator to become a synchronous compensator

3. Transformer


3.1 Generator Transformer
o Pauwels Trafo 11.8/132 KV 80 MVA generator transformer
o DY connection, OFAF cooling with on load tap changer
o Full scheme of electrical protection

3.2 Unit Transformer
o GEC 11,800/433 V 250KVA unit transformer
o DY connection, ONAN cooling
o Full scheme of electrical protection

4. Other Auxiliaries

4.1 Inverter
o 110V AC and DC power supply to essential auxiliaries and control
o 56 Hoppecke battery cells

4.2 Temperature Monitoring and Data Acquisition System
o High scanning speed Digilink 4+ monitor system
o MS DOS base data acquisition program KVIEW
o Real time data colour graphics, trenching and event logging

4.3 Control Room Layout
o AC and DC auxiliary switch board
o Essential supply cubicle
o Dual battery charger cubicle
o Fire detection and protection cubicle
???Control/extinguishing and detection modules
o Local control panel suit
    Synchronisation, excitation, generator protection panel
    Contains all the necessary relays and circuitry
    Governor panel
    Contains the Mk 2 modular governor system
    Turbine control cubicle
    Auto start/run up control
    Auxiliaries control
    Monitoring equipment cubicle
    Vibration monitor
    Turbine thrust wear monitor
    Temperature monitor
    Torch lit amplifier
    Dual flame detection module

4.4 Fire Fighting Equipment
o Thorn Automatic fire fighting and detection system
o Halon system covers Turbine and Generator enclosure, Control room, Battery room and Fuel annex.
o Water spray system protects Generator transformer, Unit transformer and Lubrication oil cooler.

5. Document and Others

5.1 Documentation
o Full set of Operation, Maintenance Volumes
o Full set of sub-contractor literature

5.2 Turbine maintenance special tools
o Special tools are available with list

5.3 Turbine and generator spares
o Spares are available with list

5.4 Work Shop
o one 19.38 tons overhead crane
o one 6.12 tons overhead crane

6. Options 6.1 Black start Diesel Generator

o Ruston Diesel V16 turbo charged diesel generator
o Rated at 2,600 KVA, 3.3 KV, 750 rpm
o automatic voltage regulated
o Associated switch gear and switch board

Contact Milt Fyre for more details.
Phone: 503-595-5418