50MW Steam Turbine Generator

THE ENGLISH ELECTRIC COMPANY LIMITED
STEAM TURBINE NO. S.T. 1143

BRIEF TECHNICAL PARTICULARS

Maximum Continuous Rating 50 M.W.
Speed 3,600 r.p.m.
Inlet Steam Pressure 1,450 psig
Total Temperature 1000 F
Vacuum at Exhaust (Bar 30") 29" Hg. at 50MW
Final Feed Temperature When feed heating 449 F at 50MW

As shown on the accompanying Sectional Arrangement Drawing R277/621 the turbine is of the two cylinder impulse-reaction type.

The machine comprises an H.P. cylinder having one Curtis stage and 17 impulse stages and double flow L.P. cylinder having a first stage of the impulse type and five reaction stages in each flow.  The H.P. cylinder is so arranged that the steam flow is away from the rest of the turbine and alternator.  By tending to balance the thrusts, the arrangement relieves the load on the single thrust bearing provided to control the axial flow of the whole turbo-alternator unit.

The H.P. and all but the last stage of the L.P. blades are mounted in grooves in the forged steel rotors. The final stage of the L.P. has, for each flow, a forged steel disc which is shrunk and keyed on to the shaft.  The last row L.P. blades are of the side entry type in which each root is in a separate groove cut across the disc head.

The nozzles of the H.P. turbine are carried in built up type diaphragms.  Cast iron diaphragms are provided to carry the first stage impulse nozzle and the final stage fixed blading in the L.P. cylinder.

Steam packed labyrinth glands are provided for each cylinder.

Turbine/Generator Details

Unit Design Rating 50 MW
In Service Date November 1961, Manufactured by English Electric
Operating Hours to Date 85,273, last operation 1995
Number of Starts to Date Cold Starts 267, Hot Starts 788
Design Steam Conditions Steam Flow 415,000 pph, Inlet steam pressure/temperature - 1450 psig/1000 F, Exhaust Pressure 1.0 Abs.
Turbine Details Single flow HP Turbine, 1 Curtis stage, 17 rows impulse blading, with four extractions.  Double flow LP Turbine - 6 rows reaction blading with one extraction.
Generator Details Hydrogen Cooled Generator at 45 psig pressure. 13800 volts, 58824 KVA 2462 A, 0.85 P.F.
Maintenance History HP Turbine last inspection 1989.  LP Turbine last inspection 1985