STEAM TURBINE GENERATOR DATA

 Steam Turbine - General Electric - Number 87451:
Rated 60000 KW - 3600 RPM - 21 Stages
Steam Pressure 1250 PSIG - Temp 950 Degree F - Exhaust Pressure 1.5"HG ABS

Generator:

No.6792055 Hydrogen Cooled: Rating: Capacity:
Type ATB 2 Poles 60 Cycles Gas Pressure 0.5 PSIG 15.0 PSIG
3 PH Y Connected for 13800 Volts KVA 70588 81176
Excitation 250 Volts Kilowatts 60000 69000
Temperature Rise Not to Exceed: Armature Amps 2953 3396
60 DEG C on Armature by Detector Field AMPS 635 700
85 DEG C on Field by Resistance Power Factor 0.85 0.85