STEAM TURBINE GENERATOR DATA

Steam Turbine - General Electric - Number 93365
Rating 122000 KW - 3600 RPM - 20 Stages
Steam Pressure 1450 PSIG - Temp 1000 Degree F - Exhaust Pressure 1.5 HG ABS

Generator:

No.6862947 Hydrogen Cooled: Rating: Capability: Capacity:
Type ATB 2 Poles 60 Cycles Gas Pressure 0.5 PSIG 15.0 PSIG 30 PSIG
3 PH Y Connected for 13800 Volts KVA 105882 121764 132353
Excitation 250 Volts Kilowatts 90000 103500 112500
Temperature Rise Not to Exceed: Armature Amps 4430 5094 5537
60 DEG C on Armature by Detector Field AMPS 935 1027 1094
85 DEG C on Field by Resistance Power Factor 0.85 0.85 0.85

Contact Lane Kadel for more details. Phone: 503-239-5157
Fax: 503-239-5136
lane@rmaglobal.com

Click Here to Return to POWER PLANT INDEX



sales@rmaglobal.com   Phone: (503) 239-5157   Fax: (503) 239-5136   Copyright 1995-2003: RMA Inc.