22.5MW Coal Plant for sale
60Hz.  13.8kV

Contact Milt Fyre    milt@rmaglobal.com  503-351-9898
(Click here for images)

 

22.5MW Complete coal plant built in 1948 consisting of 2 steam turbine generators (15MW and 7.5MW) and 3 boilers rated at 650psig, 700F and 150k/150k/200k//lbs/hr.    A 4th boiler rated a 200psig and saturated steam used for supplemental steam.    Generator 1 is rated at 18.7MW and Generator 2 is 9.375MW 60Hz. 13.8kW. (Click here for details and images.)  

 

TURBINE #1 WESTINGHOUSE STEAM TURBINE INSTRUCTION BOOK 1250-C5
RATED KW 15000
MAX KW 18750
INITIAL PRESS. 650
INITIAL TEMP. 725 DEG. F
EXH. PRESS. 50#
EXT. PRESS. 50#
RPM 3600
SERIAL 5-A-3556-1

TURBINE #2 WESTINGHOUSE STEAM TURBINE
RATED KW 7500
MAX KW 9375
INITIAL PRESS. 650 PSIG
INITIAL TEMP. 750 DEG. F TT
EXH. PRESS. 50 PSIG
RPM 3600
INSTR. BOOK 1190C14
SERIAL 15A2064-1

GENERATOR #1 WESTINGHOUSE AC GENERATOR
KVA 18750
VOLTS 13800
AMPS 783
% POWER FACTOR 80
PHASE 3
CYCLES 60
RPM 3600
EXC. AMPS 280
EXC. VOLTS 250
DEG. C TEMP RISE 60S 75R
INSTR. BOOK 5449
SERIAL IS30P575


GENERATOR #2 WESTINGHOUSE AC GENERATOR
AIR COOLED
KVA 9375
POWER FACTOR 0.80
STATOR AMPERES 392
STATOR VOLTS 13800
ROTOR AMPERES 168
EXCITER VOLTS 250
TEMPERATURE RISE WITH 40 DEG. C AMBIENT WILL NOT EXCEED -
STATOR 60 DEG. C, ROTOR 85 DEC. C
CONNECTED Y PHASE 3
CYCLES 60 RPM 3600
MAX. INLET WATER TEMP. 95 DEG. F
INSTR. BOOK 7890
SERIAL IS64P996


POWER PLANT CAPACITIES

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTINUOUS

 

 

 

 

NAMEPLATE

4 HR. MAX .

SUSTAINABLE

YEAR

 

PRESSURE

TEMPERATURE

CAPACITY

CAPACITY

CAPACITY

INSTALLED

BOILER

PSI

DEG F

1000 LB/HR

1000 LB/HR

1000 LB/HR

 

 

 

 

 

 

 

1948

1

650

750

150

140

130

 

 

 

 

 

 

 

1948

2

650

750

150

140

130

 

 

 

 

 

 

 

1952

3

650

750

200

185

175

 

 

 

 

 

 

 

1960

4

200

Saturated

200

185

175

 

 

 

 

 

 

 

 

 

TOTAL

 

700

650

610

 

 

 

 

 

 

 

 

TURBINE

RATED KW

 

 

 

 

 

 

 

 

 

 

 

1948

1

 15,000

 

 

 

 

 

 

 

 

 

 

 

1960

2

 7,500

 

 

 

 

 

 

 

 

STEAM *

ELECTRIC

 

CURRENT HIGH SUSTAINED SUMMER LOADS

325,000 LB/HR

17,500  KW

 

 

 

 

 

 

 

 

CURRENT HIGH SUSTAINED WINTER LOADS

 

420,000 LB/HR

17,000  KW

 

(WINTER HEATING LOAD IS 30,000 - 50,000 LB/HR)

 

 

 


The superheated steam from the three - 650 psig boilers is used to generate power.   The steam enters the two Turbines at 650 psig. The process steam is extracted at 50 and 150 psig.  Some steam is condensed to meet electrical requirements when they are high and process steam requirements are low. PRV 's (pressure reducing valves) are also used to supply steam to the complex when steam load cannot be maintained through the turbine. The maximum generating capacity while operating on the three high-pressure boilers is 22,500 KW.
  
Boiler #4 is operated at 200 psig.  The steam from this boiler is used primarily during the winter months when the steam demand is the greatest and when the other boilers are not operational.
  
The power plant is continuously connected to the Power Company through a separate connection near .    This service is maintained to improve reliability and purchase power from the Power Company when their rate is less than our cost to generate. The Power Company can supply 17,000 kW through this connection. We can also supply the wastewater  treatment plant (1,000 - 1,200 kW) through a separate service.   Through these two services all the necessary power is supplied to the complex.
 


 

BOILER #1

 

LLR #1424

 

 

BOILER #3

 

LLR #1426

BABCOCK & WILCOX COMPANY 

 

 

BABCOCK & WILCOX COMPANY 

 

INTEGRAL - FURNACE BOILER:

 

 

STEAM BOILER UNIT:

 

 

CAPACITY 150,000 LB/HR.

 

 

 

CAPACITY 200,000 LB/HR.

 

 

DESIGN PRESSURE  750 PSI

 

 

DESIGN PRESSURE  750 PSI

 

STEAM TEMPERATURE  750 DEG . F

 

STEAM TEMPERATURE  750 DEG . F

BUILT - 1947

 

 

 

 

BUILT - 1954

 

ECONOMIZER:

 

 

 

 

INTEGRAL FURNACE BOILER:

 

CONTRACT NO. ED-1321

 

 

 

CAPACITY 200,000 LB/HR

 

 

DESIGN PRESSURE  750 PSI

 

 

DESIGN PRESSURE  750 PSI

 

H.S. SQUARE FT  2618

 

 

 

STEAM TEMPERATURE  750 DEG . F

NATIONAL BOARD NO. 14690

 

 

BUILT - 1954

 

 

 

BUILT - 1947

 

 

 

 

 

 

 

 

 

 

ECONOMIZER:

 

 

WATER COOLED WALL:

 

 

 

CONTRACT NO. EC-1871

 

 

CONTRACT NO. F-992

 

 

 

DESIGN PRESSURE  750 PSI

 

DESIGN PRESSURE  750 PSI

 

 

H.S. SQUARE FT  2320

 

 

H.S. SQUARE FT.  2732

 

 

 

NATIONAL BOARD NO. 18754

 

NATIONAL BOARD NO. 14690

 

 

BUILT - 1954

 

 

 

BUILT - 1947

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BOILER:

 

 

 

SUPERHEATER:

 

 

 

CONTRACT NO. F-2369

 

 

CONTRACT NO. SH 7862

 

 

 

DESIGN PRESSURE  750 PSI

 

DESIGN PRESSURE  750 PSI

 

 

H.S. SQUARE FT.  8055

 

 

NATIONAL BOARD NO. 14690

 

 

NATIONAL BOARD NO.  18754

 

BUILT - 1947

 

 

 

 

BUILT - 1954

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WATER COOLED WALL:

 

 

 

BOILER #2

 

LLR #1425

 

CONTRACT NO. F-2369

 

 

 

 

 

 

 

 

DESIGN PRESSURE  750 PSI

 

BABCOCK & WILCOX COMPANY 

 

 

H.S. SQUARE FT.  3340

 

 

INTEGRAL - FURNACE BOILER:

 

 

NATIONAL BOARD NO. 18754

 

CAPACITY 150,000 LB/HR.

 

 

 

BUILT - 1954

 

 

 

DESIGN PRESSURE  750 PSI

 

 

 

 

 

 

 

STEAM TEMPERATURE  750 DEG . F

 

SUPERHEATER:

 

 

BUILT - 1947

 

 

 

 

CONTRACT NO. SH 9360

 

 

 

 

 

 

 

 

DESIGN PRESSURE  750 PSI

 

ECONOMIZER:

 

 

 

 

NATIONAL BOARD NO. 18754

 

CONTRACT NO. EC-1321

 

 

 

BUILT - 1954

 

 

 

DESIGN PRESSURE  750 PSI

 

 

 

 

 

 

 

H.S. SQUARE FT  2618

 

 

 

 

 

 

 

 

NATIONAL BOARD NO. 14691

 

 

 

 

 

 

 

BUILT - 1947

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BOILER #4

 

LLR #1427

WATER COOLED WALL:

 

 

 

 

 

 

 

 

CONTRACT NO. F-992

 

 

 

BABCOCK & WILCOX COMPANY 

 

DESIGN PRESSURE  750 PSI

 

 

INTEGRAL - FURNACE BOILER:

 

H.S. SQUARE FT.  2732

 

 

 

CAPACITY 200,000 LB/HR.

 

 

NATIONAL BOARD NO. 14691

 

 

DESIGN PRESSURE  250 PSI

 

BUILT - 1947

 

 

 

 

STEAM TEMPERATURE -  SAT .

 

 

 

 

 

 

 

BUILT - 1961

 

 

 

SUPERHEATER:

 

 

 

 

 

 

 

 

CONTRACT NO. SH 7862

 

 

 

CONTRACT NO. FH 2849

 

 

DESIGN PRESSURE  750 PSI

 

 

BOILER H.S. SQUARE FT.  13103

 

NATIONAL BOARD NO. 14691

 

 

NATIONAL BOARD NO.  20739

 

BUILT - 1947

 

 

 

 

BUILT - 1961

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Contact Milt Fyre    milt@rmaglobal.com

Email: sales@rmaglobal.com   Phone: (503) 595-5418   Fax: (503) 635-0091   Copyright 1995-2008: RMA Inc.