24MW MAN Cogeneration Power Plant for Sale

HFO, 50Hz. 

Contact Milt Fyre    milt@rmaglobal.com 503-351-9898

 

(Click here for PDF file of images)

Cogeneration Power Plant:   Operating with 2x9L58/64 MAN B&W Diesel AG Engines and Auxiliary Equipment for sale to be moved by the purchaser.  The plant burns HFO and has a total of 10,000 operating hours.  The plant is in good operating condition and operation data is available.

Engine:   Manufacturer MAN B&W Type 2 x 9 L58/64 Output 2 x 12170 KW at 100 % load  (ISO 25°C air temp., 1 bar air pressure, 25° cooling water temp.) Specific fuel oil consumption (sfoc)*: 181,5 g/kWh Lubricating oil consumption** 0,37 g/kWh +20% Speed 428 rpm Exhaust gas temp // volume 361 °C +-/15% // kg/h.

Tolerance of sfoc ?? 3% related to mechanical output without attached pumps, according to ISO 3046/1:1995. ** Tolerance of lubricating oil consumption ?? 20 % related to Using fuel oil with LHV = 42,700 kJ/kg. mechanical output at 100 % load.

Alternator:  Manufacturer Siemens Type:1DK5536-3DE 07-Z Output 15200 kVA Frequency 50 Hz Speed 428,6 rpm Voltage 11 kV Cos ph 0,8

HFO Treatment:   Manufacturer Alfa laval Type SU 500 Nominal Output 3 M3/h Operation Temp Max 155 oC

Viscosimat:   Manufacturer KUPKE+WOLF GMBH Type V92

Lubrication Treatment:  Manufacturer BOLL&KIRCH Type 6.48

Control / Monitoring System:   Manufacturer KUHSE Type Control System

Heat Recovering Boiler:   Manufacturer AALBORG INDUSTRIES OY Type AV-6N Output Steam Pressure / Temperature 7,5 bar / 173 °C 5,7 t/h per engine

Heat Exchanger:   Manufacturer Type Output Hot Water Pressure / Temperature.   GEA Ecoflex gmbH Plate Type Heat Exchanger bar / 90 °C 130 m3/H

Cooler:  Manufacturer Type No of cooling fans Nominal Load / max ambient air Temperature GEA KTO-GVO 50 S 2 MOTEURS 1500 TR/MN 18,5 26°C


Transformer:  Manufacturer Type  BEST TRANFORMER BALKESR/ TURKEY 2 x YT16000/36 YNd5, IN/OUT  31.5kV/11kV, Frequency 50Hz,  Load 16000 kVA 


Station Transformer:  Manufacturer Type BEST TRANFORMER BALKESR/ TURKEY VT,  IN/OUT  31.5kV/0.4 kV, Frequency 50 Hz, Load 2500 

 

Compressors:  Manufacturer Type Neuenhauser Kompressoren GmbH Air cooled compressormodule 3-stages 2x40.2.3.00.03.10.23 30 bar / 100 m3/h

Air Filter:  Manufacturer Type  LOCKER AIR-MAZE AUTOMAZE600 EM Automatic Air Bath Filter


Special Tools related to the engines:   Injection Pressure testing device, Hydraulic Pressure Pump, and special-standart tools for assembly and disassembly, and a good spare part stock 

 

Cogeneration Power Plant operating with 2x9L58/64 MAN B&W Diesel AG Engines.   MAN B&W Diesel Engines operating with HFO-6 Serial Nos: 1110271-1110272 Electrical Output : app. 2x12170 kWh


Auxiliaries:   SEMENS Generators, SEMENS Parallel/Synchronisation Equipments, SEMENS 0,4 kV panels.   Neutral Resistance rooms,   Transformers from 2x11 kV/31.5 kV , 31.5/0.4 kV    Cooling Towers made by GEA Exhaust Gas Waste Heat Steam Boilers made by AALBORG INDUSTRIES OY (2x5,7ton/h).   Air Intake Filters Starting Air Compressors 3xHFO and 2xLube Oil Seperators made by ALFA LAVAL 2xHT.    Cooling Water Pumps, 2xLT Cooling Water Pumps Main LO Pumps,etc.   2x HFO Viscosity Modules with booster pumps, filters, steam reg. valves, 2xHFO and DO Main Ring Pumps with Filtering Modules, 1x Fresh Oil Tank, 1xUsed Oil Tank, 1x Engine Cooling Water Coll. tank, 1xLeak HFO and LO tanks, 2x3000t, 2x165 t, 1x500t fuel tank. 1x LO Automatic Filtering Module, etc.

 

 

Contact Milt Fyre    milt@rmaglobal.com

Email: sales@rmaglobal.com   Phone: (503) 595-5418   Fax: (503) 635-0091   Copyright 1995-2010: RMA Inc.