5.2MW Solar Taurus T-60 Gas Turbine Generator Sets
for sale

3 Mobile (trailer-mounted) Sets and 7 Regular Sets
50/60Hz.

These are low hour mobile GTG sets in excellent condition.

Table 1. Performance Data ISO*, XQ5200 Mobile Power Unit
                                                English                       Metric
Power Output                   5,200 kWe                     5,200 kWe
Heat Rate                         11,263 Btu/Kwe-hr       11,900 kJ/Kwe-hr
Fuel Flow (LHV)             59.8 mmBTU/hr            59.8 mmBTU/hr
Emissions, NOX              25 PPMvd                     25 PPMvd
                                         5.84 LBM/Hr                2.65 kG/Hr
CO                                    50 PPM vd                   50 PPM vd
                                         7.1 LBM/Hr                  7.1 LBM/Hr
Gen. Voltage                     12.47or 13.8 kV           3.22 kG/Hr
Gen. Frequency                 60 Hz                           60 Hz
Voltage Steady State         0.5%                            0.5%
Short Circuit                     300% for 10 sec.          300% for 10 sec.
* ISO, Sea Level. 60% relative humidity, Natural Gas Fuel, No inlet or exhuast losses.

Table 2. Dimensional Data & Weights, Installed, XQ5200 Mobile Power Unit
                                              English                         Metric
Length                                     48 ft.                             14.6 meters
Width                                      21 ft.                             6.4 meters
Height                                     26.6 ft.                          8.1 meters
Installed Weights
Turbine Section                     118,000 lbs                    54 M tons
PCR Trailer                           55,000 lbs                     25 M tons

Table 3. Dimensional Data & Weights, Installed, XQ5200 Mobile Power Unit
                                              English                         Metric
Natural Gas Fueled
Gas Pres.                                 250 PSIG                 172 KPAG
Max. Gas Demand                   1,400 SCFM            39.6 M3/Min
Foundation
Gravel Compacted to 2,500 lbs/ft2 120 kPA
Fuel Quality
Clean Dry Fuel Per Solar
Spec ES 9-98

BASIC PACKAGE: Solar T-60 ( B.O.M )

The Taurus 60 Industrial Power Generator (IPG) is a compact, rugged gas turbine generator set that has been designed to meet the requirements for industrial and utility power generation applications. The unit is provided as a completely integrated module ready for installation. The gas turbine engine, gearbox, generator, control system, fuel system, lubrication system, start system, and ancillary equipment needed for site operation on natural gas are included with each unit.

Each package includes a sound attenuated enclosure for the turbine generator and a PCR control building to house all generator and turbine control functions.

Approximate overall dimensions are: 32 feet, 0 inches (9753 mm) long 8 feet, 0 inches (2438 mm) wide.
Approximate height of package is 10 feet, 8 1/4 inches (3258 mm) and may vary with ancillary equipment and generator selection. Four lifting gussets are provided on each section.
Drip pans are welded beneath the package frame to collect potential liquid spills. The drip pans also provide a tight seal for containment of fire suppression agent for packages supplied with an enclosure.
Tube Fittings. All tube connections use compression fittings. Tubing and fittings are 316 stainless steel. Piping. Package piping is designed and fabricated to ANSI B31.3.

ELECTRICAL SYSTEM
The Taurus 60 IPG generator set is designed to comply with the requirements of the National Electrical Code.  Unless otherwise noted package motors and heaters are rated for 460 VAC, 60 Hertz, 3 phase. Motor space heaters are provided for motors over 5 hp (3.75 kW) and are rated for 120 VAC, 60 Hertz, 1 phase.
Fire Detection and Suppression System. The gas turbine enclosure will be provided with ultra violet fire detectors and fire monitoring system. The fire suppression system agent is C02. In the event of a fire being detected within the unit, the unit will shutdown, the enclosure ventilator louvers will close, and horns will sound. Gas Detection System. Gas detection monitors are provided in the turbine enclosure. Upon detection of 20% LEL, alarms will sound. Upon detection of 75% LEL, the unit will shut down and all louvers will open, and all ventilator fans will activate.

GAS TURBINE ENGINE
The Taurus 60 gas turbine engine is a single shaft axial flow engine. The output gearbox, including accessory drive pads, is a separate, close-coupled unit located at the inlet end of the turbine. The engine assembly consists of: Gear unit with accessory drive pads. Air inlet collector with flexible flange connection. Axially split case in the vertical plane, eleven-stage axial flow compressor with variable temperatures. Geometry control on inlet guide vanes and first two rows of stators Annular SoLoNox combustor with 12 lean premix fuel injectors.  Three-stage turbine assembly, Turbine exhaust collector. 

The components of the Taurus 60 engine are maintained in accurate alignment by mating flanges with pilot surfaces and are bolted together to form a rigid assembly. The speed-reducing gearbox is driven by the compressor rotor shaft. Accessory pads drive the main lube oil pump and other accessories, depending on the application, and support the starter motor.   The gas turbine output shaft is mechanically connected to both the compressor and turbine sections of the engine to form a "solidor "singleshaft configuration. This feature enhances speed stability and response under constant and varying load conditions -- a highly desirable feature in generator applications requiring precise frequency control.

SPEED REDUCING GEARBOX
The speed-reducing gearbox is an industrial design manufactured by Solar specifically for the Taurus 60 IPG generator set. The gearbox mounts directly on the Taurus 60 gas turbine to reduce engine speed to 1800 rpm (60 Hz).

GENERATOR
Generator Rating. Generator nameplate rating per NEMA standards is 6,625 Kva at 0.8 power factor (5,300kw) 13,800 volts at 104°F (40°C), 3281 ft (1000 m) elevation for continuous duty. The generator is rated so that the generator will not limit turbine performance over the range of site ambient temperatures.

Deviation Factor [maximum]
Harmonic Content [maximum]
Telephone Interference Factor
Balanced Residual

Voltage Drift. The change in voltage will not exceed 1.0% over a 30-minute period when the generator is operating at rated voltage and 0.8 to 1.0 power factor and with a constant load between no load and full rated load.
Generator Voltage. The generator output is 13,800 Volt, 3 phase, 60 Hz.
Insulation conforms to NEMA class F.

TURBINE START SYSTEM
A direct drive AC motor is provided to start the Taurus 60 engine. A variable frequency drive [VFD] motor controller is included for installation in the motor control center [MCC]. 3 phase AC power is required at 460VAC, 60Hz, 250 Amperes. The control system provides all required sequencing to quickly and reliably start the turbine.

FUEL SYSTEM
The fuel system, in conjunction with the electrical control system, includes all necessary components to control the fuel pressure, to schedule fuel flow during start-up, and to modulate fuel flow during operation.
Natural Gas Fuel. A natural gas fuel system is provided with all components necessary to maintain turbine speed to provide a constant generator output frequency and/or load depending on the generator set mode of operation. Solar's Specification ES 9-98 contains the specific fuel requirements.
The natural gas fuel system includes: Primary fuel shutoff valve, Pilot-operated secondary fuel shutoff valve

Electronic fuel actuator
10-micron pilot gas filter
2 fuel injector assemblies
Valve check pressure switch
High gas fuel pressure shutdown switch
Gas strainer System requirements for the natural gas fuel are as follows:
Requires a constant supply of gas at a maximum flow demand rate of 32.2 nm3/min (1200 scfm) at 1725-kpa-gauge (225 psig) minimum pressure. Gas fuel pressure is used to operate the fuel system pilot valve.
The gas fuel should be free of sulfur, contaminants, entrained water, and liquid hydrocarbons
Gas fuel must conform to Solar's Specification ES 9-98

LUBE OIL SYSTEM
A complete lube oil system suitable for operation with lube oil conforming to Solar's Specification ES 9-224 is included. The lube oil system provides oil to the bearings in the Taurus 60 gas turbine engine, gearbox and generator. Instrumentation, flow control and on frame piping are included.
Main Lube Oil Pump. An engine driven lube oil pump is provided with suction strainer. Post Lube Backup Pump. A 1.5hp (1.1 kW) AC motor driven pump is provided to supply post operation lube oil flow in the event of power failure. Power is provided by a 24 VDC battery system through a VFD/ inverter.
Drain Line Sight Glasses. Sight glasses are provided on the drain lines from all gas turbine, generator and gearbox bearings. Note that some of the gas turbine bearings have a common drain line.
Lube Oil Tank. A 420-gallon operating capacity carbon steel lube oil tank is provided. The lube oil tank is integral with the package frame. Lube oil level indicator, fill connection with inlet strainer and drain connections are included.
Lube Oil Tank Heater. A thermostatically controlled 4.5 kW lube oil tank heater is provided. Electric power requirements are 460 V, 60 Hz, three phase.
Lube Oil Vent Separator. An off skid mechanical coalescer element is provided to remove oil vapor from the lube oil tank vent. Recovered oil drains back to the lube oil tank. Interconnect piping between the frame flanges and the vent separator is not included in Solar's scope. The vent separator is nominally rated for less than 0.2 gallons/day (0.76 L/day) oil loss.
Lube Oil Cooler. An air/oil lube oil cooler is provided. The fan is driven by a 3.7 kW AC motor. The lube oil cooler is designed for off skid installation. Interconnect piping between the frame flanges and the lube oil cooler is included according to current design.
Lube Oil Type. Lube oil is not included. The lube oil supplied must be consistent with the requirements of Solar specification ES 9-224.
Lube Oil Filter. Single 5-micron oil filter units are provided with drain, fill and vent valves.

CONTROL SYSTEM
Solar Control System.
The Turbotronic control system is provided and is a highly integrated programmable logic controller [PLC] based control system. The control system is installed on the package frame to minimize interconnect wiring.
The control system includes a microprocessor, remote communications modules; chassis based and flex input/output modules, line synchronization module, power supplies and a hardware backup shutdown system.
The control system provides for control of all phases of package operation to include start and shutdown sequencing, normal operation, and malfunction shutdown.
Vibration Monitoring. Vibration monitoring is provided to include three proximity probes, one per bearing, on the Taurus 60 engine. One accelerometer is provided with the gearbox. Two velocity transducers, one per bearing is provided with the generator. Preset warning indications and malfunction shutdown initiation are provided.
Temperature Monitoring. Temperature monitoring is provided to include the Taurus 60 engine thrust bearing, lube oil drains, and lube oil header and the generator bearings and stator windings. Preset warning indications and malfunction shutdown initiation are provided. Ambient, lube oil tank and enclosure temperatures are also monitored.
Audible Alarm. An audible alarm horn is provided to sound whenever the unit has an alarm or shutdown condition. A horn silence push button is mounted on the face of the control panel.
Local Display. The control system is installed on the package frame in weatherproof enclosures. A digital control panel [DCP] with all of the necessary switches and indicators is provided. In addition to display of "first outmalfunctions, the DCP can display:
System summary/normal running data o System status
Digital display of engine and generator parameters
Alarms and Shutdowns
Engineering Units. Temperature data is displayed in °F. Pressure data is displayed in pounds per square inch [psi].
Language. Package labels and screen displays are in English.
Supervisory Interface. An RS 232C/422-interface module is provided to give the user's supervisory computer access to the Turbotronic control system data. Limited control capability is provided to allow the supervisory computer to start and stop the unit, reset alarms, and raise/lower speed and load set points. The communications protocol is Allen
Bradley's DF1. The interface module may be located up to 10,000 feet (3,048 meters) from the turbine control system and located up to 50 feet (15 meters) from the supervisory computer for the RS 232C module or 4,000 feet (1,219 meters) for the RS 422 module. The modules are "table topunits and require 120 Vac, 50/60 Hz power.

GENERATOR CONTROL AND MONITORING
Integrated monitoring and control of the generator is provided using a specially designed module in the PLC to receive input data from potential and current transformers. The system calculates real and reactive power, power factor and the variables required for synchronization.
Automatic Synchronizing. An automatic synchronizer is provided with the control system to automatically synchronize the unit to the bus through push-button control on the digital control panel [DCP] or by receipt of an appropriate remote signal. A synch check relay is provided as an additional permissive and for backup protection.
Motorized Voltage Adjust. Raise/lower voltage push button control is provided on the digital control panel to control a motorized potentiometer for voltage control. An additional raise/lower switch, supplied by others, may be used to control voltage from a remote location.
KW Controller. A kW import controller is provided to control the real load (kW) on the generator set while operating in parallel with a utility or other large source. The kW controller monitors the load imported from the utility source and adjusts the generator set fuel flow to maintain a pre-set level of imported power on the utility at all times. This control mode is for applications where it is desired to prevent any power from being exported to the utility. Protection against excessive kW load while in parallel with a large source is provided by the control system "T5temperature limiter. The kilowatt load level select switch and adjustment is located on the digital control panel.
KVAR/Power Factor Controller. A kvar/power factor controller is provided to maintain a constant reactive load (WAR) output or constant power factor (pf) on the generator set while the unit is operating in parallel with a utility or other large source. The controller applies a signal directly to the voltage regulator adjust circuit to maintain a constant reactive load or power factor with changes in the infinite bus voltage level. The system incorporates a set point adjust rheostat to set the desired WAR or pf, a selector switch to choose WAR or pf control mode, and a switch to turn the controller on and off

ADDITIONAL ANCILLARY EQUIPMENT
The following additional ancillary equipment is also provided for the turbine-generating package:
(a) Neutral Ground Resistor
(b) Auxiliary Load Transformer (13.8 kv:480 V, 60 Hz). This transformer eliminates the requirement for an alternate 480VAC shore power supply.
(c) (C) Liquid Fuel Boost Pump (with dual fuel option)
(d) XI. DRAWINGS
(e) One set of standard drawings is provided with each turbo machinery package.
(f) XII. OPERATION AND MAINTENANCE MANUALS
(g) One set of operation and maintenance manuals are provided with each turbo machinery package.

SECTION 3
POWER CONTROL ROOM (PCR) BUILDING FOR A SOLAR TAURUS 60 POWER GENERATOR SET:

Utility Grade 15KV class metal clad paralleling switchgear:

The Power Control Room Building contains the following equipment:
PCR HVAC system
Generator Main Circuit Breaker 15KV
Auxiliary Transformer Feeder Circuit Breaker
Bus pts, Feeder cts, Metering cts and pts, and Protective Relay Module
Lightning Arrestor and Surge Capacitor
Motor Control Center (Serves Turbine Generator 480VAC Auxiliary Loads)
120VDC Turbine Generator Battery System with Charger
Dedicated 120VDC Switchgear Battery System with Charger

Note:
The above description is a general outline configuration of a Solar T-60 mobile package as built by Solar. The offered equipment may have further options as was ordered by seller when the equipment was built. Final "as built" build of material is subject to verification but will meet or exceed the above description.