5.67MW Solar Turbomach Taurus T60 (5 Units)  Gas Turbine Generators for Sale
New    50Hz.  Dual Fuel (Gas & HSD) Water Injection

Asking $2.6 million(USD) FOB Seaport

Contact Milt Fyre    milt@rmaglobal.com    503-351-9898

5.67MW Solar Turbomach Taurus T60 (5 Units available)  Gas Turbine Generators for Sale.  The units are new.  50Hz.  Dual Fuel (Gas & HSD) Water Injection.  

Industrial Gas Turbine Taurus 60 (T60-7901), Compressor assembly, Turbine and combustor assembly, Combustion system

Reduction Gear: Two stage, star compound epicyclic type.

Coupling & AC Synchronous Generator 50 Hz, 11 kV, Brushless excitation system.
Protection IP21, Insulation class H, Temperature Rise class F, Self-ventilated air cooled.
Accessories and instrumentation.

Starting System Hydraulic start motor, Hydraulic oil filter, Hydraulic pump.

Dual Fuel System - Natural Gas Fuel System- Gas filter, Fuel shutoff valves, Fuel control valve, Fuel manifold, Instrumentation, Internal piping, Gas flow meter.

Liquid Fuel System - Duplex filter, High pressure speed controlled pump, Filter, Fuel shutoff valves, Fuel manifold, Air assist system, Drain tank, Instrumentation, Internal piping.

Water Injection System - Water inlet filter, Motor driven pump, Valves and control devices.

Lubrication System - Lube-oil tank, Lube-oil heater, Main lube-oil pump, Pre/post lube-oil pump, Lube oil cooler, duplex lube-oil filter, Electrostatic vapour extractor, Indicators and instrumentation Internal piping.

GT Compressor Washing System off-line and on-line, Water tank, Water manifold, Instrumentation & Internal piping, On-line washing system.

Base Frame w Vibration Dampers 6.

Sound Enclosure 85 dB(A) at 1m ,green field conditions Air filter housing, Alarms & Instrumentation.

Ventilation air filter system: Electric Motor driven air blowers, Pneumatically driven air shutters.

TUMATRONIC S4 Turbine Control System - Backup Failsafe PLC, PC "Real time", PC HMI with touch screen TFT, Profibus acquisition modules.

Generator Control, Synchro. & Auxiliary System - Generator measurement unit, Generator voltage regulation, Generator protection, SPM Synchroniser, Vibration monitoring system, Gas leakage detection system, CosPhi Card.

Control System Interface - Signal exchange, Standard connection with supervisory control systems, Desktop remote PC - installed in customer control room. Client supervision control system interface, data processing excluded.

AC Supply System, DC Supply System Starting Cubicle.
24 V/DC battery charger, 24 V batteries 1 set, 24 V distribution bus.

Fire Detection & Extinguishing Equipment - Electronic control unit, Infra-red detectors.
Release push-button, Horn & light signalisation, Spray nozzles, CO2 bottles.

TECHNICAL PERFORMANCE PARAMETERS
Gas Turbine Generator Set Mode T60 Fuel Natural Gas

Fuel Composition Methane (CH4) % Vol. 84.4999
Ethane (C2H5) " 9.0000
Propane (C3H8) " 3.0000

I - Butane (C4H10) " 2.0000
I - Pentane (C5H12) " 0.2500
Nitrogen (N2) " 1.2500
Sulphur Di Oxide (SO2) " 0.0001

Reference Conditions Site Altitude m.a.s.l. 230; Relative Humidity % 60
Engine air inlet temperature ºC 15
Inlet duct pressure loss mm H2O 75
Exhaust duct pressure loss mm H2O 250
Frequency 50 Hz Power factor 0.80 (lagging)
Generator Voltage 11 kV Min. fuel gas pressure 1500 kPa(g)

Guaranteed Gas Turbine Performances (without water injection)
Electric power at alternator terminals kW 5'165; Heat Rate kJ/kWh 11'845

Nominal Exhaust Data at Full load.
Exhaust gas temperature °C 508; Exhaust gas flow Kg/h 73989 Exhaust heat cooled to 170ºC KWth 7583

Guaranteed Emissions at full load.
NOx emissions with water injection < 100 ppmv @ 15%O2 CO emissions < 50 ppmv @ 15%O2,

Sound Guarantees Sound pressure level at 1 meter distance dBA 85

Notes:

1. The fuel composition will be as above and in accordance with Solar Fuel Specifications - ES-9-98.

2, The performance test of the Gas Turbine is based on ISO 2314 and PCT 1985-22.

3. The turbine compressor will be cleaned prior to the performance test. Air filters shall be in new and clean condition.

4. The plant is operated in continuous duty, under normal operating conditions.

5. For NOx guarantee water to fuel ratio is 0.3 kgH2O/kg fuel and the GT is at Full Load.

6. NOx is measured as NO and is based upon 1/2 hour measuring average value.

7. CO is based upon 1/2 hour measuring average value.

8. For sound guarantee the sound level is measured from 1 m. from equipment, 1.5m above ground level and the background noise level must be at least 10 Dba lower than the guaranteed value.

9. If the ambient conditions are other than the reference conditions, the measured values will be
corrected using the correction curves and detailed performance test procedure described in supplier's offer.

10 Power and Heat Rate are calculated as average upon the plant GTs.

 

 

 

 

Contact Milt Fyre    milt@rmaglobal.com

Email: sales@rmaglobal.com   Phone: (503) 595-5418   Fax: (503) 635-0091   Copyright 1995-2012: RMA Inc.